Question

I tried everything to establish communications between my PC and the CPU with no luck. I do have the power LED on and I am powering the processor with 120 VAC. I have confirmed I have the correct communications cable and the latest DirectSOFT32 programming software. What else can I check?

Answer

If you are powering the processor power supply with 120 VAC, make sure you have installed the shorting link on the bottom two terminals for 100-120 VAC operation. Clich here for the Directsoft Troubleshooting manual.


FAQ Subcategory: CPU & Programming

This item was last updated on 2004-02-13
Document ID: 934


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.