AutomationDirect Logo OPC/DDE server Frequently Asked Questions


« Return to the FAQ index

Question Upgraded from DS DDE Server to DS Data. Now my client gets error: "Remote data not accessible" and then asks to start DDE. Reference line says "REF" which according to the manual means "DS Data Server is not running."
Answer The reason for this is that DS DDE Server and DS Data have different ServiceNames. DS DDE Server's ServiceName is "DSDDE." DS Data's ServiceName is "DSDATA." Thus there are two solutions to get links working again: · Modify client's reference of the ServiceName from "DSDDE" to "DSDATA". · Edit the ds400.ini file and under the heading "[DSData]" change the "ServiceName=DSDATA" to "ServiceName=DSDDE" If you choose the second option above, then by restarting DS Data you will cause it to now have a ServiceName of "DSDDE" and all the links and tags created for DS DDE Server will now work.

FAQ Subcategory:

This item was last updated on 08-28-2003
Document ID: 978


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.