Question What does the temperature spec of the drive mean? What is the conversion from Celsius to Fahrenheit?
Answer The spec is –10*C to 50*C. When the operating temperature is between 40*C and 50*C the following events must happen. 1.) The carrier frequency must be reduced to 2.1 kHz 2.) The output must be derated to 80% 3.) The top cover of the drive must be removed (this also nullifies the NEMA rating of the drive) The conversion from Celsius to Fahrenheit is: F = 1.8 x C + 32.0

FAQ Subcategory: None

This item was last updated on 09-25-2001
Document ID: 879


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.