Question How do I size a SJ300 drive for the 0Hz function?
Answer With this function the drive produces 200% torque on start up. The drive must be derated by one drive size. If it is not, the drive will trip out on over current.

FAQ Subcategory: None

This item was last updated on 08-24-2001
Document ID: 778


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.