| Question | What drive power cable do you recommend and why? |
| Answer | Beldon 29500 – 29507 cables are specifically designed for use with VFDs. Using the wrong cable can increase the detrimental effects from ringing due to capacitive coupling. Thermoplastic insulation like in standard THHN cable will break down over time with connectivity from inverters to motors. The standing waves caused by PWM will cause high voltage potential on single conductors. This renders corona (reflective/ringing voltage) in the air gaps between the conductors, which could breakdown and cause a system failure. |
FAQ Subcategory:
This item was last updated on 02-23-2004
Document ID: 771
The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.