Question

Can the sinking type 4 - 20mA analog output of the Click PLC be used to provide a speed reference signal for the GS series drives?

Answer

The GS2 and Durapulse drives are compatible with the 4 - 20mA sinking analog output of the Click PLC. The GS1 drive is not compatible as the discrete and analog inputs share the same common connection. Wiring should be as follows:

  • + (18 - 30VDC, PS) connected to AI (analog input of drive)
  • - (18 - 30VDC, PS) connected to ACOM of Click PLC
  • ACM (analog common of drive) connected to DAxI of Click PLC



    FAQ Subcategory: None

    This item was last updated on 2010-07-23
    Document ID: 1312


    The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.