Question Can I use a 3 pole starter for a single phase motor?
Answer Yes, but use all three poles of the starter. Wire one of the incoming power lines through two of the poles in series per the manufacturer's instructions. Wire from the T_ terminal of one pole to the L_ terminal of the other pole.

FAQ Subcategory:

This item was last updated on 02-17-2004
Document ID: 1026


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.