Is there any way to define a single Item to address a block of V-memory within DSDATA?

Answer

Unfortunately this is not possible with DS Data and the ECOM. It was an engineering decision given the then pros and cons. There must be a one-to-one correspondence between PLC data types and OPC/DDE reference types. So the problem begins with the fact that there's no block (or array) data type in the Direct Logic (DL) PLCs sold by Automation Direct. Without this data type in the PLC, there's no way for any DDE/OPC client to create an Item that can reference a range of data in the PLC.


FAQ Subcategory: None

This item was last updated on 2003-08-28
Document ID: 970


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.