Question

Can I use the MOP type terminal speed control with acceleration and deceleration times of less than 1 second? E.G. settings 14 and 15 for DI3-DI6 on GS2 and 14 and 15 for DI3 and DI4 on the GS1.

Answer

For the GS1, GS2, and GS3 drives

No.

When the acceleration time or deceleration time is set below 1 second, there is not enough time for the cpu to process the speed change. If the lower times are required, use any of the other methods of speed control available.


FAQ Subcategory: None

This item was last updated on 2021-02-16
Document ID: 950


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.