Question

Do the PS series power supplies have an isolated ground or is the negative leg of the output tied to ground either directly or indirectly by a passive or active component?

Answer

The output is isolated from the input, the -Vout is floating.

If you need to meet EMC emission standards, you would have to install external Y-capacitors from
  • Neutral to PE (protective earth)
  • Live to PE
  • +Vout to PE
  • -Vout to PE



FAQ Subcategory: None

This item was last updated on 2021-02-17
Document ID: 939


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.