Question

For single phase operation, can I use a smaller than rated contactor if I run the L conductor parallel through all three poles?

Answer

We do not recommend this practice. Do not exceed the rated capacity of what a single pole can handle. The operation will not close simultaneously which will allow a contact to take the entire load. This practice will lead to premature failures.

It is not uncommon to do this for greater reliability of the contactor, but the single pole specs must be met for all poles used.



FAQ Subcategory: None

This item was last updated on 2004-02-17
Document ID: 883


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.