Question

The lights brighten when my motor starts?

Answer

It is normal with some >220 vac circuits with neutrals that have lighting and motors on the same feeder. This is very brief though. If it is prolonged, > 1 second, this could mean that your neutral connection is loose. A loose neutral can lead to a voltage imbalance in the phases.


FAQ Subcategory: None

This item was last updated on 2004-02-18
Document ID: 836


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.