AutomationDirect Technical Support
AutomationDirect | Direct Sales in US and Canada | 1-800-633-0405

General Drives Questions Frequently Asked Questions AutomationDirect Logo


Question

Can I use wire-nuts on motor leads?

Answer

As long as the FLA of the motor is under the spec of the wire-nut, yes. Understand that wire-nuts are susceptible to vibration. And most institutions frown on using wire-nuts on anything other than residential projects. Always check with your local NEC code regulations.


FAQ Subcategory: None

This item was last updated on 2021-02-17
Document ID: 835


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.


Copyright © 1999- AutomationDirect.com. ALL RIGHTS RESERVED