AutomationDirect Technical Support
AutomationDirect | Direct Sales in US and Canada | 1-800-633-0405

Hitachi Drives Frequently Asked Questions AutomationDirect Logo


Question

What considerations do I need to investigate for running multiple motors on one inverter?

Answer


Please review the following:


 Speed reference – all motors must be run at the same speed. They have the same frequency and voltage.
 Inverter Size – the size must be based on total current and not HP. If the aggregate is close, always round up.
 Motor Protection – an output line reactor and manual motor starters functioning as thermal motor protectors on each motor branch.



FAQ Subcategory: None

This item was last updated on 2001-08-23
Document ID: 805


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.


Copyright © 1999- AutomationDirect.com. ALL RIGHTS RESERVED