Question

What parameters do I change in the SJ300 drives for a centrifugal load?

Answer

1. A041 automatic
2. A044 01 reduced torque
3. A082 correct line voltage
4. B002 1 second
5. B012 120%
6. B013 00 reduced torque
7. B088 01 restart at motor speed
8. F002 40 seconds
9. F003 40 seconds




FAQ Subcategory: None

This item was last updated on 2001-06-11
Document ID: 777


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.