Question

What parameters do I change in the L100/SJ100 drives for a centrifugal load?

Answer

1. A41 automatic
2. A44 01 reduced torque
3. A82 correct line voltage
4. B02 5 seconds
5. B12 FLA + 20% in amps
6. B13 00 reduced torque
7. B88 01 restart at motor speed
8. F02 40 seconds
9. F03 40 seconds



FAQ Subcategory: None

This item was last updated on 2001-06-11
Document ID: 776


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.