Question

Can I run my application at extremely low speeds?

Answer

Three major problems exist with both conventional methods of motor control and VFD control.
  1. When a motor is directly coupled and run at low speed it becomes very inefficient. One could go with a high torque motor that is significantly larger than the standard (including higher cost), and would have the same results most of the time.
  2. Typical motors do not cool themselves well at extremely low speed. The added heat buildup in the windings can cause premature motor failure. Check with the motor manufacturer for more details.
  3. The other issue is load inertia, which is larger than that of the motor. These effects increase greatly with a transmission system that is sloppy. A speed reducer or gearbox should be employed to solve this problem. It will match the inertial changes and increase the efficiency. ADC does offer various Mechanical Power Transmission options.



FAQ Subcategory: None

This item was last updated on 2021-03-24
Document ID: 775


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.