Question

No matter what I change on the SJ100 or L100 I cannot get the remote operator to start/stop or change speeds, why?

Answer

Depress the MON button until you see F/R SELECT or F-SET SELECT, use the one arrow to position cursor on right hand side. When positioned, arrow up or down until you see REM. When parameter is changed, depress the STR button to make the change permanent. Changing both function listings to REM will allow you to operate remotely. Depress the FUN and then the MON buttons to get back to the FS 000.0 0.0Hz display. The FWD RUN and REV RUN buttons should now be active as well as changing FS to desired speed.



FAQ Subcategory: None

This item was last updated on 2001-05-30
Document ID: 746


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.