Why can I not get any Control Output from my PID loop?

Answer

Most likely you haven't entered a high limit for your Control Output in the PID setup. The default is 0 and the maximum is 4095 binary. Your must enter something in this field (Word+31) from the PID setup or from ladder. You should also check your Control Output word (Word+5) to see if you are actually getting Control Output. If this value is changing then make sure you are writing this value to the physical output device. This will most likely be an analog card or Time-Proportioning ladder for a discrete output point.


FAQ Subcategory: PID

This item was last updated on 2001-11-07
Document ID: 52


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.