AutomationDirect Technical Support
AutomationDirect | Direct Sales in US and Canada | 1-800-633-0405

DL105 Frequently Asked Questions AutomationDirect Logo


Question

What is the accuracy of the timer instructions?

Answer

The accuracy of the timer instruction is the same as the accuracy of the clock generator used for the microprocessor in the DL105. The accuracy of the clock generator is +/- 50 PPM. So the accuracy of the timer instruction is: +/-50 PPM * 60 sec * 60 min * 24 hr = +/- 4.32 seconds (per day)



FAQ Subcategory: CPU & Programming

This item was last updated on 2021-01-21
Document ID: 42


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.