Question

My DL105 drops out of run mode intermittently. What's wrong?

Answer

This problem occurs only with the relay output version of the DL105. If the relay is driving an inductive load, the load needs to be suppressed using any MOV or TVS. This prevents EMF (noise) from traveling back to the relay and will keep the DL105 from dropping out of run mode.

Please see AN-MISC-032 for information on correcting relay transient issue.


FAQ Subcategory: CPU & Programming

This item was last updated on 2021-01-21
Document ID: 38


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.