Question

The run indicator on the CPU is flashing. What's wrong?

Answer

The CPU has gone into update mode. This can be caused by an electrical spike to the incoming power or by the relay outputs, if powering an inductive load without using proper surge suppression.

To correct this problem, you will need update the firmware. You will need the Koyo Support Tool and DL105 Firmware file

If your issue was relay output related, please see AN-MISC-032 for correcting relay transient issue.


FAQ Subcategory: CPU & Programming

This item was last updated on 2022-09-01
Document ID: 33


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.