Question

My inputs X0-X3 and/or my outputs Y0-Y1 are not working. What's wrong?

Answer

The PLC is most likely in a high speed counter mode. When in high speed counter mode inputs X0-X3 and/or Y0-Y1 will not act as normal I/O. To reset the processor to treat X0-X3 and Y0-Y1 as normal I/O, Initialize the scratchpad by:
  • PLC >> SETUP >> INITIALIZE SCRATCHPAD
Be aware that initializing the scratchpad will reset the system V-memory to defaults. System V-memory contains parameters such as retentive ranges, DV-1000 setup parameters, etc.


FAQ Subcategory: CPU & Programming

This item was last updated on 2021-01-22
Document ID: 31


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.