Question

I cannot get my Allen-Bradley Micrologix PLC to communicate with my Touch Screen. I keep getting communication timeout errors. I have everything configured like the manual states on page A-6 of the Screen Creator manual.

Answer

The setup on page A-6 is correct except that Error Detection should be set to “CRC” to communicate properly with an AB Micrologix PLC.


FAQ Subcategory: None

This item was last updated on 2000-10-17
Document ID: 261


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.