When I try to communicate to my 250 CPU on port 2 RS422, I keep getting the error (#2965 CH3 Time Out error Check the cable and PLC station number).

Answer

If you are using our D2-DSCBL-2 make sure that the wires are connected as shown on page A-4 of the Screen Creator manual and that blue/white is tied to green/white, and blue is tied to green.

If you are making your own RS422 cable make sure that it is connected as follows:


15 Pin Touch screen
7 ------------------ SG
10 ----------------- RD
9 ------------------ RD+
6 ------------------ SD-
13 ----------------- SD+

Jumper 11-14 and 12-15 on the 15 pin port.




FAQ Subcategory: None

This item was last updated on 2000-10-17
Document ID: 260


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.