My module will occasionally fail when I power up my system. Why does this happen?

Answer

Normally this is caused by an inadequate power supply corrupting the memory. When determining the size of a power supply be sure to include ALL sources of energy consumption and also account for the surge these devices require. For example an OP-613 requires 1.5 Amps (for 2 milliseconds) at start-up, but after start-up needs only 90 mA at 24VDC to function.




FAQ Subcategory: None

This item was last updated on 2000-10-17
Document ID: 183


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.