Question

When I have my Optimate module connected to a DL205, my LCD and/or light bars work, but my pushbuttons don't...why?

Answer

The Optimate module cannot WRITE to the PLC's memory when the 205 is in Run configuration, therefore only the LCD and/or light bars visually function. The DL 205 should be reset to the 'term' position in order for the Optimate module to write to it.



FAQ Subcategory: None

This item was last updated on 2000-10-17
Document ID: 182


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.