Question

If I don't have a battery in the Click, will I lose the program?

Answer

All CLICK PLC units have a non-volatile FLASH ROM to store the downloaded ladder program and project file. The FLASH ROM will retain the ladder program indefinitely. You do not have to have a battery.

However, the Click data registers are stored in the SRAM (volatile) memory, that is backed up by a super capacitor. The super capacitor will hold the memory contents for a short period of time, like a power cycle.

Super Capacitor Data Hold Time
    For C0 Clicks (page 2-9 of the Manual )
    • Non-Ethernet Click -> 7 days.
    • Ethernet Clicks -> 1 hour.

    For C2 Clicks (page 2-5 of the Manual )
    • 1 hour

If you plan on having power off the Click for longer then the super capacitor can hold data, and want to retain the data memory, you will need to use the optional battery.
  • C0 Battery -> D2-BAT-1
  • C2 Battery -> D0-MC-BAT



FAQ Subcategory: None

This item was last updated on 2022-10-21
Document ID: 1641


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.