Question

Can K-Sequence, DirectNet or Non-Sequence be used with the RS-485 ( 2-wire) configuration for port 2 on a D2-250(-1), D2-260 or D2-262?

Answer

Modbus is the only protocol that can be used with RS-485 (2-wire)
DirectNet can be used with RS-422 (4-wire).
K-Sequence and Non Sequence can only be used with RS-232.


FAQ Subcategory: None

This item was last updated on 2021-03-24
Document ID: 1638


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.