What Exception Responses do the Solo temperature controllers support?

Answer

Response Codes [MB address + (function code + 80H) + Error code]
Error Code -- Error Definition
01H - function code is not supported
02H - Illegal function address
03H - Illegal read/write word count

Response Codes [MB address + (function code + 80H) + Error code]
Error Code -- Error Definition
01H - function code is not supported
02H - Illegal function address
03H - Illegal read/write word count
04H - Data process fail
09H - Checksum error

Exception 4 is often caused by Writes to the Solo, but not having parameter CoSH set to 1 or Yes can cause this error.


FAQ Subcategory: None

This item was last updated on 2021-02-26
Document ID: 1599


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.