Question

Is it possible to connect out of the RS485 Port 3 on Click to one of the Advanced stepper drives ( 4850 or 80100)?

Answer

While it is possible, the cost and wiring issues make a 2nd Click a much easier solution.



Click Port 3:
+ to TX+ on ISOCON Term block D
- to TX- on ISOCON Term block D
GND to GND Term block D

1/2 Duplex dipswitches both on on bottom bank of ISOCON.
5V and 0V Bias dipswitches on as well.
Must power cycle ISOCON after dipswitches are changed.

ISOCON Port A Pin 4 (TX) to Pin 5 on 4850 drive (RX)
ISOCON Port A Pin 3 (RX) to Pin 3 on 4850 drive (TX)
ISOCON Port A Pin 1 to Pin 2 on 4850 drive (GND on both)NOTE: Do NOT use Pin 6 on ISOCON Port A. It is not the same potential as Pin 1, though the ISOCON manual shows them as being the same.



FAQ Subcategory: None

This item was last updated on 2017-10-19
Document ID: 1592


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.