Question

In the Solo controller, if I have a 4-20mA input and output 1 is a 4-20mA output, the output works fine when tested by a meter. however, when I connect the output to my 4-20mA input device the Solo output goes to maximum current and won't change.

Answer

The Solo units have no electrical isolation between the 4-20mA input and the 4-20mA output. For devices that require electrical isolation, connection to those devices cause the output to go to maximum and not adjust. You will either have to isolate the current output of the Solo or use a different controller that provides the electrical isolation your device requires.


FAQ Subcategory: None

This item was last updated on 2017-05-24
Document ID: 1583


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.