Can I use reed switches with AC inputs?

Answer

We do not recommend this, as the inrush of the AC input can cause the reed switch contact to fail.


Also the reed switch can arc when opening causing a voltage higher than than your system supply.

This higher voltage can quickly damage AC inputs, which have a maximum rating of 132 vac.

Reed switch flutter or bounce can make this condition even worse.


FAQ Subcategory: None

This item was last updated on 2015-08-19
Document ID: 1549


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.