Question

Why can I see my P3-550 CPU in the PAC Connections Dialog, but I can not connect to it?

Answer

The most common reason for this is a conflict in the Subnet Mask in your Ethernet configuration between your PC or Laptop and the P3-550. The discovery method used to find connected CPUs on the network is different from the method used to connect and communicate to the CPU, which explains why you may be able to see the CPU, but not connect to it. See the Communications Ethernet topic.


FAQ Subcategory: None

This item was last updated on 2014-09-19
Document ID: 1528


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.