Q:My standard driver sheet(s) is locking up / updating slowly. What is the problem?

Answer

A: Standard driver sheets can be problematic when using non-sequential blocks of data, and PoV can actually fail to update the entire sheet repeatedly.

Create multiple sheets if you need different blocks of data (note that standard driver sheet must be a single data type in any case).
For example, if you need Modbus Holding Registers 1-40 and 200-230, you need to create 2 driver sheets, one for 1-40, and the other for 200-230. This holds true for all drivers and data types (bits might not be AS susceptible, but following this procedure prevents the issue completely).

Using BlinkSlow or BlinkFast (600 or 200 ms, respectively) provides for easy Read/Write triggers.


FAQ Subcategory: None

This item was last updated on 2014-07-29
Document ID: 1526


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.


Copyright © 1999- AutomationDirect.com. ALL RIGHTS RESERVED