AutomationDirect Technical Support
AutomationDirect | Direct Sales in US and Canada | 1-800-633-0405

DL205 Frequently Asked Questions AutomationDirect Logo


Question

"CTRIO Workbench says my H2-CTRIO2 needs a firmware update" or "I updated the firwmare in my H2-CTRIO2, and now it's stuck in booter mode"

Answer

Older versions of CTRIO Workbench (2.1.x or earlier) will incorrectly identify a CTRIO2 as a CTRIO that needs a firmware update.
Do NOT attempt this. You must get the latest CTRIO Workbench version from HostEng.com (2.2.x or later).CTRIO Workbench

Unzip and install this updated version of Workbench. If you already attempted the firmware update and your CTRIO2 is now stuck in booter mode, you will need to do the same, PLUS, get the latest CTRIO2 Firmware from their website and try to update the CTRIO2 firmware again. You might have to try several times, but if it still won't get out of booter mode, you will need to contact Returns Department.


FAQ Subcategory: None

This item was last updated on 2021-01-22
Document ID: 1512


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.