Question

Can I use two Rhino power supplies in parallel for redundancy?

Answer

In most cases you can connect two Rhino series power supplies in parallel, however you should always refer to the online data sheets to determine if the specific powers supplies in question can be used in parallel operation. Parallel operation requires the use of either a redundancy module like the PSP24-REM240S or the PSB60-REM20S or a decoupling diode with power ratings suitable for the application.
The Vishay VT4045C is good example of a decoupling diode and can be sourced from many online electronic component suppliers.



FAQ Subcategory: Power, I/O, and Wiring

This item was last updated on 2014-02-19
Document ID: 1504


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.