AutomationDirect Technical Support
AutomationDirect | Direct Sales in US and Canada | 1-800-633-0405

Point of View Software Frequently Asked Questions AutomationDirect Logo


Question

The Trend History does not work after adding or removing tags in the Trend worksheet.

Answer

When a tag is inserted or removed FROM a Trend worksheet, the format of the history files (*.HST) is modified.
The same HST file cannot have two different formats, otherwise the data will not be retrieved from it properly by
the Trend object. If you need to add or remove tags for history files, there are two valid procedures: Create a new
Trend Worksheet or delete the old *.HST files.


FAQ Subcategory: None

This item was last updated on 2013-11-19
Document ID: 1493


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.