The screens are shown on the Web Thin Client (Browser); however, the data (tags values) are not read from the Server.

Answer

Make sure the parameter in the Web Data column from the application tags database is set as Server instead of
Local. The tags set as Server keep the same value in the Server and in the Web Thin Client (Browser). The tags
set as Local have independent values in the Server and in the Web Thin Client (Browser).
 Caution: You must execute the Tools → Verify Application command after modifying the tags settings.
Otherwise, the changes will not be updated in the web files.


FAQ Subcategory: None

This item was last updated on 2013-11-19
Document ID: 1491


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.