Question

What communications are available in Do-more if the DCM and CoPro modules aren't supported?

Answer

The H2-SERIO and H2-SERIO-4 take over many features of DCM and CoPro.

H2-SERIO-4 can do Modbus, K-seq, ASCII, or customer can create his own protocol. There are 3 ports available on either module, all independently configurable.
  • H2-SERIO has 3 RS-232 ports.
  • H2-SERIO-4 has 2 RS-232 and one RS-485 port.

Multiple modules of either or both types are supported.


FAQ Subcategory: None

This item was last updated on 2021-03-23
Document ID: 1424


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.