Can I set the CTT series Timer/Counter/Tach to Flicker Mode?

Answer

Yes, this is called "Repeat Cycle 2" in the CTT Manual starting on page 3-20

To use Repeat Cycle
  • select [mode] longer than 3 sec
  • pick time using the up/down keys
  • select t mode
  • pick up or down counting/timing using the up/down keys
  • select t otmd
  • pick rCY2 using the up/down keys
  • select t Unit
  • pick your time base using the up/down keys
  • select rtSr
  • pick 1 or 20 ms reset using the up/down keys
  • select tnPtLC
  • pick PnP or nPn using the up/down keys
  • press [mode] for longer than 3 sec to go to run mode.


[mode] selects the SET1 or SET2 on and off times.

RST2/Start input will start Flicker mode

[RESET] or RST1 input stops the flicker mode Note! Set1 time must be longer than Set2 time.

Note: If you jumper the start input to +12 VDC (configured for PnP) or 0V (configured for nPn) it will start the cycle on power up after the CTT stabilizes.


FAQ Subcategory: None

This item was last updated on 2021-02-18
Document ID: 1408


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.