Question

Can I use a P3-HSI module to read the SureServo line-driver encoder output?

Answer

Yes! The P3-HSI can accept both differential (line-driver) or single-ended (sink/source) as input signals. There is a wiring diagram in the P3-HSI insert for line driver signals.

  1. OA(servo) to 1A (HSI)
  2. /OA to 1A-
  3. OB to 1B
  4. /OB to 1B-



FAQ Subcategory: High-speed count / Pulse out

This item was last updated on 2012-04-27
Document ID: 1399


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.