Question

Is it possible to wire multiple safety switches in series to the e-stop/safety gate safety relay inputs?

Answer

In the cases where the safety input circuit forms a loop (terminal S11 - S12 and S21 - S22), the total voltage drop in that circuit should not exceed 2 Vdc, which at 30mA sensing current, allows for 60 ohms maximum resistance.

Also, there may be repercussions to the Safety Integrity Level of the overall system that would fall under the customer's responsibility to determine.


FAQ Subcategory: None

This item was last updated on 2011-05-18
Document ID: 1372


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.