Question

Can I reset a T1H-EBC100 to factory default IP address (0.0.0.0) ?

Answer

How to reset T1H-EBC100 to default addresses (0.0.0.0)
  1. Power down the T1H-EBC100
  2. Remove any modules to the right of the T1H-EBC100 (unclip and slide them on the dinrail)
  3. Open the cover on the right side of the T1H-EBC100
  4. Turn on dipswitch 0 (farthest to the left)
  5. Power cycle the T1H-EBC100
  6. Turn off dipswitch 0
  7. Close the cover over the dipswitches
  8. Reconnect any modules to the T1H-EBC100
  9. Power up the T1H-EBC100
  10. Open NetEdit3 and assign a new IP address



FAQ Subcategory: None

This item was last updated on 2021-01-25
Document ID: 1351


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.