Question

What is the proper power budget figures for the different 305 bases and style.

Answer

It depends on the base and style;
  • The -1 Bases show the figures for 60°C rating
  • The figures for the D3-08B and D3-10B are for 0-50°C
  • Total current for D3-0B & D3-05BDC cannot exceed 2300 mA
  • Ratings are in milliAmps(mA)



5VDC9VDC24VDC
D3-05B1400800500
D3-05BDC1400800500
D3-08B14001700600
D3-10B14001700600
D3-05B-17002000600
D3-08B-17002000600
D3-10B-17002000600
D3-10BDC7001700600


Please refer to the user manuals for the 305 or 350 for the most accurate information


FAQ Subcategory: None

This item was last updated on 2021-02-26
Document ID: 1345


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.