Question

I cannot connect to a C-more for programming, my ping times are very long or I cannot ping (VPN etc). Can you change the timeouts?

Answer

For EA7 (all) and EA9 (prior to V6.0)

    You will have to edit EA_.INI with Windows Notepad. It is located in the directory you installed the C-More software

    Once you open the file, go to the [App] section of the file and add this at the bottom:
      PING=1
      PINGTIMEOUT=xxxx
      PanelTimeout=xxxx

    PING -> 1 = enables. 0 = disables
    PINGTIMEOUT= is in milliSeconds
    PanelTimeout= is in Seconds

    You need to re-start the software anytime you change the values above.

For EA9 (V6.0 and newer versions)

In the "Ethernet Connection Setup", click on the "Remote Link List" and add a connection. In the connection dialog, it will allow you to specify longer timeouts and retry settings


FAQ Subcategory: None

This item was last updated on 2021-02-09
Document ID: 1329


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.