Question

How does the PSM24-BCM360S prevent deep discharge of the battery(batteries)?

Answer

The BCM monitors output voltage when the mains supply is off.

When the battery voltage drops to 20VDC +/- 0.5VDC the BCM shuts off the whole system until the mains power returns.
When mains power returns, the BCM turns the output back on and uses the surplus capacity from the power supply to recharge the battery.



FAQ Subcategory: None

This item was last updated on 2010-07-20
Document ID: 1324


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.