Question

Can you change the position of the alarm message banner?

Answer

The alarm banner position cannot be changed, it resides at the bottom of the screen.

The alarm banner is unique in that it will display on any screen automatically.

If you need customized alarm messages (position etc), you could make a background screen with a lookup text object or add the object to all screens that would need this. You would need to address multiple alarms with PLC logic to select the messages one at a time etc. You would have to handle the queueing and display of the alarms manually. The advantage of the alarm banner is that the panel handle this sequencing for you.


FAQ Subcategory: None

This item was last updated on 2021-01-26
Document ID: 1234


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.