Question

How can I connect the encoder output of the SureServo to the inputs of a CTRIO module?

Answer

The encoder output of the SureServo is line-driver ( 5V TTL). It won't work directly to the CTRIO or CTRIO2 modules.

You would need to use a High Speed Optical Isolators, like the FC-ISO-C or the FC-ISO-D

Host Engineering does also make an adapter board CTRIO-TTLANNEX that will allow you to connect a TTL signal to the CTRIO2. Please contact Host Engineering, Inc at "support@hosteng.com"


FAQ Subcategory: None

This item was last updated on 2021-03-02
Document ID: 1200


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.