Can I configure a DL06 to do high speed counting and generate high speed pulse output?

Answer

a. You can do High Speed Inputs or High Speed outputs, but not both.
b. Mode 10 allows you to configure two high speed counters, up to 7 KHz.
c. Mode 20 allows you to configure a quadrature counter, which allows counting in clockwise and counter clockwise directions (or count up or down), up to 7 KHz.
d. Mode 30 allows you to do high speed pulse outputs up to 10 KHz. It supports three profiles: trapezoidal, registration and velocity.
e. Click here for Appendix E of DL06 User Manual.



FAQ Subcategory: High-speed count / Pulse out

This item was last updated on 2009-03-17
Document ID: 1175


The information provided in the AutomationDirect knowledge base is provided "as is" without warranty of any kind. AutomationDirect disclaims all warranties, either express or implied, including the warranties of merchantability and fitness for a particular purpose. In no event shall AutomationDirect or its suppliers be liable for any damages whatsoever including direct, indirect, incidental, consequential, loss of business profits or special damages, even if AutomationDirect or its suppliers have been advised of the possibility of such damages. Some states do not allow the exclusion of limitation of liability for consequential or incidental damages so the foregoing limitation may not apply.